Site requirements for Outposts racks
An Outpost site is the physical location where your Outpost operates. Sites are only
available in select countries and territories. For more information, see, AWS Outposts rack FAQs
This page covers the requirements for Outposts racks. If you are installing an Aggregation, Core, Edge (ACE) rack, your site must also meet the requirements listed in Site requirements for Outpost ACE racks.
For the requirements for Outposts servers, see Site requirements for Outposts servers in the AWS Outposts User Guide for Outposts servers.
Facility
These are the facility requirements for racks.
-
Temperature and humidity – The ambient temperature must be between 41° F (5° C) and 95° F (35° C). The relative humidity must be between 8 percent and 80 percent with no condensation.
-
Airflow – Racks draw cold air from the front aisle and exhaust hot air to the back aisle. The rack position must provide at least 145.8 times the kVA of cubic feet per minute (CFM) airflow.
-
Loading dock – Your loading dock must accommodate a rack crate that is 94 inches (239 cm) high by 54 inches (138 cm) wide by 51 inches (130 cm) deep.
-
Weight support – Weight varies by configuration. You can find the weight for your configuration specified in the order summary at the rack point loads. The location where the rack is installed and the path to that location must support the specified weight. This includes any freight and standard elevators along the path.
-
Clearance – The rack is 80 inches (203 cm) high by 24 inches (61 cm) wide by 48 inches (122 cm) deep. Any doorways, hallways, turns, ramps, and elevators must provide sufficient clearance. At the final resting position, there must be a 24 inch (61 cm) wide by 48 inch (122 cm) deep area for the Outpost, with an additional 48 inches (122 cm) of front clearance and 24 inches (61 cm) of rear clearance. The total minimum area required for the Outpost is 24 inch (61 cm) wide by 10 feet (305 cm) deep.
The following diagram shows the total minimum area required for the Outpost, including clearance.
-
Seismic bracing – To the extent required by regulation or code, you will install and maintain appropriate seismic anchorage and bracing for the rack while it is in your facility. AWS provides floor brackets that provide protection for up to 2.0G of seismic activity with all Outposts racks.
-
Bonding point – We recommend that you provide a bonding wire / point at the rack position so that the AWS-certified technician can bond the racks during installation.
-
Facility access – You will not change the facility in a way that negatively affects the ability of AWS to access, service, or remove the Outpost.
-
Elevation – The elevation of the room where the rack is installed must be below 10,005 feet (3,050 meters).
Networking
These are the networking requirements for racks.
-
Provide uplinks with speeds of 1 Gbps, 10 Gbps, 40 Gbps, or 100 Gbps.
For bandwidth recommendations for the service link connection, see Bandwidth recommendations.
-
Provide either single-mode fiber (SMF) with Lucent Connector (LC), multimode fiber (MMF), or MMF OM4 with LC.
-
Provide one or two upstream devices, which can be switches or routers. We recommend two devices to provide high availability.
Network readiness checklist
Use this checklist when you are gathering the information for your Outpost configuration. This includes the LAN, WAN, and any devices between the Outpost and local traffic destinations, and the destination in the AWS Region.
Uplink speed and ports
An Outpost has two Outpost network devices that attach to your local network. The number of uplinks each device can support depends on your bandwidth needs and what your router can support. For more information, see Physical connectivity.
The following list shows how many uplink ports are supported for each Outpost network device, based on the uplink speed.
- 1 Gbps
-
1, 2, 4, 6, or 8 uplinks
- 10 Gbps
-
1, 2, 4, 8, 12, or 16 uplinks
- 40 Gbps or 100 Gbps
-
1, 2, or 4 uplinks
Fiber
The following fiber types are supported:
-
Single-mode fiber (SMF) with Lucent Connector (LC)
-
Multi-mode fiber (MMF) or MMF OM4 with LC
Depending on the uplink speed and the type of fiber that you choose, the following optical standards are supported.
Uplink speed | Fiber type | Optical standard |
---|---|---|
1 Gbps |
SMF |
– 1000Base-LX |
1 Gbps |
MMF |
– 1000Base-SX |
10 Gbps |
SMF |
– 10GBASE-IR – 10GBASE-LR |
10 Gbps |
MMF |
– 10GBASE-SR |
40 Gbps |
SMF |
– 40GBASE-IR4 (LR4L) – 40GBASE-LR4 |
4 x 10 Gbps breakout application |
MMF |
– 40GBASE-ESR4 – 40GBASE-SR4 |
100 Gbps |
SMF |
– 100G PSM4 MSA – 100GBASE-CWDM4 – 100GBASE-LR4 |
4 x 25 Gbps breakout application |
MMF |
– 100GBASE-SR4 |
Link aggregation control protocol (LACP) is required between the Outpost and your network. You must use dynamic LAG with LACP.
The following VLANs are required for each Outpost network device. For more information, see Virtual LANs.
Outpost network device | Service link VLAN | Local gateway VLAN |
---|---|---|
#1 |
Valid values: 1-4094 |
Valid values: 1-4094 |
#2 |
Valid values: 1-4094 |
Valid values: 1-4094 |
For each Outpost network device, you can choose whether to use the same VLANs or different VLANs for the service link and local gateway. However, we recommend that each Outpost network device have a different VLAN from the other Outpost network device. For more information, see Link aggregation and Virtual LANs.
We also recommend redundant layer 2 connectivity. LACP is used for link aggregation and is not used for high availability. LACP between the Outpost network devices is not supported.
Each of the two Outpost network devices requires a CIDR and IP address for the service link and local gateway VLANs. We recommend allocating a dedicated subnet for each network device with a /30 or /31 CIDR. Specify a subnet and an IP address from the subnet for the Outpost to use. For more information, see Network layer connectivity.
Outpost network device | Service link requirements | Local gateway requirements |
---|---|---|
#1 |
– Service link CIDR (/30 or /31) – Service link IP address |
– Local gateway CIDR (/30 or /31) – Local gateway IP address |
#2 |
– Service link CIDR (/30 or /31) – Service link IP address |
– Local gateway CIDR (/30 or /31) – Local gateway IP address |
The network must support 1500-bytes MTU between the Outpost and the service link endpoints in the parent AWS Region. For more information about the service link, see AWS Outposts connectivity to AWS Regions.
The Outpost establishes an external BGP (eBGP) peering session between each Outpost network device and your local network device for service link connectivity over the service link VLAN. For more information, see Service link BGP connectivity.
Outpost | Service link BGP requirements |
---|---|
Your Outpost |
– Outpost BGP Autonomous System Number (ASN). 2-byte (16-bit) or 4-byte (32-bit). From your private ASN range (64512-65534 or 4200000000-4294967294). – Infrastructure CIDR (/26 required, advertised as two contiguous /27s). |
Local network device | Service link BGP requirements |
---|---|
#1 |
– Service link BGP peer IP address. – Service link BGP peer ASN. 2-byte (16-bit) or 4-byte (32-bit). |
#2 |
– Service link BGP peer IP address. – Service link BGP peer ASN. 2-byte (16-bit) or 4-byte (32-bit). |
UDP and TCP 443 must be statefully listed in the firewall.
Protocol | Source Port | Source Address | Destination Port | Destination Address |
---|---|---|---|---|
UDP |
443 |
Outpost service link /26 |
443 |
Outpost Region's public routes |
TCP |
1025-65535 |
Outpost service link /26 |
443 |
Outpost Region's public routes |
You can use an AWS Direct Connect connection or a public internet connection to connect the Outpost back to the AWS Region. For Outpost service link connectivity, you can use NAT or PAT at your firewall or edge router. Service link establishment is always initiated from the Outpost.
The Outpost establishes an eBGP peering session from each Outpost network device to a local network device for connectivity from your local network to the local gateway. For more information, see Local gateway BGP connectivity.
Outpost | Local gateway BGP requirements |
---|---|
Your Outpost |
– Outpost BGP Autonomous System Number (ASN). 2-byte (16-bit) or 4-byte (32-bit). From your private ASN range (64512-65534 or 4200000000-4294967294). – CoIP CIDR to advertise (public or private, /26 minimum). |
Local network devices | Local gateway BGP requirements |
---|---|
#1 |
– Local gateway BGP peer IP address. – Local gateway BGP peer ASN. 2-byte (16-bit) or 4-byte (32-bit). |
#2 |
– Local gateway BGP peer IP address. – Local gateway BGP peer ASN. 2-byte (16-bit) or 4-byte (32-bit). |
Power
The Outposts power shelf supports three power configurations: 5 kVA, 10 kVA, or 15 kVA. The configuration of the power shelf depends on the total power draw of the Outpost capacity. For example, if your Outpost resource has a maximum power draw of 9.7 kVA, you must provide the power configurations for 10 kVA: 4 x L6-30P or IEC309, 2 drops to S1, and 2 drops to S2 for redundant, single-phase power. The three power configurations are described in the following second table.
To see the power draw requirements for different Outpost resources, choose
Browse catalog in the AWS Outposts console at https://console.aws.amazon.com/outposts/
Requirement | Specification |
---|---|
AC line voltage |
Single-phase 208 to 277 VAC; 50 or 60 Hz Three-phase:
|
Power consumption |
5 kVA (4 kW), 10 kVA (9 kW), or 15 kVA (13 kW) |
AC protection (upstream power breakers) |
For both 1N input (non-redundant) and 2N input (redundant): 30 A, 32 A, or 50 A with D-curve or K-curve circuit breaker. For 2N input (redundant) only: C-curve, D-curve, or K-curve circuit breaker. B-curve or lower is not supported. |
AC inlet type (receptacle) |
Single-phase 3xL6-30P, P+P+E, 30A or 3xIEC60309 P+N+E, IP67, 32A plugs Three-phase, Wye 1xIEC60309, 3P+N+E, IP67, clock position 7, 30A plug or 1xIEC60309, 3P+N+E, IP67, clock position 6, 32A plug Three-phase, Delta 1xNon-NEMA twistlock Hubbell CS8365C, 3P+E, center ground, 50A plug NoteThe best practice is to mate an IP67 plug with an IP67 receptacle. If that isn't possible, the IP67 plug will mate with an IP44 receptacle. The rating of the combined plug and socket will become the lower rating (IP44). |
Whip length |
10.25 ft (3 m) |
Whip - Rack cabling input |
From above or below the rack |
The power shelf has two inputs, S1 and S2, that can be configured as follows.
Redundant, single-phase | Redundant, three-phase | Single-phase | Three-phase | |
---|---|---|---|---|
5 kVA |
2 x L6-30P or IEC309; 1 drop to S1 and 1 drop to S2 |
2 x AH530P7W, AH532P6W, or CS8365C; 1 drop to S1 and 1 drop to S2 |
Not offered |
1 x AH530P7W, AH532P6W or CS8365C; 1 drop to S1 |
10 kVA |
4 x L6-30P or IEC309; 2 drops to S1 and 2 drops to S2 |
2 x L6-30P or IEC309; 2 drops to S1 |
||
15 kVA |
6 x L6-30P or IEC309; 3 drops to S1 and 3 drops to S2 |
3 x L6-30P or IEC309; 3 drops to S1 |
If the AC whips that AWS provides as previously described must be fitted with an alternate power plug, consider the following:
-
Only a certified customer-provided electrician should modify the AC whip to fit a new plug type.
-
The installation should comply with all applicable national, state, and local safety requirements, and be inspected as required for electrical safety.
-
You, the customer, should notify your AWS representative of modifications to the AC whip plug. Upon request, you will provide information about the modifications to AWS. You'll also include any safety inspection records issued by the authority having jurisdiction. This is a requirement to validate safety of the installation before having AWS employees perform work on the equipment.
Order fulfillment
To fulfill the order, AWS will schedule a date and time with you. You will also receive a checklist of items to verify or provide before the installation.
The AWS installation team will arrive at your site at the scheduled date and time. They will place the rack at the identified position. You and your electrician are responsible for performing the electrical connection and installation to the rack.
You must ensure that electrical installations, and any changes to those installations, are performed by a certified electrician in accordance with all applicable laws, codes, and best practices. You must obtain approval from AWS in writing prior to making any changes to the Outpost hardware or the electrical installations. You agree to provide AWS with documentation verifying compliance and the safety of any changes. AWS is not responsible for any risks created by the Outpost electrical installation or facility electrical wiring or any changes. You must not make any other changes to the Outposts hardware.
The team will establish network connectivity for the Outposts rack over the uplink that you provide, and will configure the rack's capacity.
The installation is complete when you confirm that the Amazon EC2 and Amazon EBS capacity for your Outposts rack is available from your AWS account.