Use OPC UA node filters in SiteWise Edge - AWS IoT SiteWise

Use OPC UA node filters in SiteWise Edge

When you define OPC UA data sources for an SiteWise Edge gateway, you can define node filters. Node filters let you limit which data stream paths the SiteWise Edge gateway sends to the cloud. You can use node filters to reduce your SiteWise Edge gateway's startup time and CPU usage by only including paths to data that you model in AWS IoT SiteWise. By default, SiteWise Edge gateways upload all OPC UA paths except those that start with /Server/. You can use the * and ** wildcard characters in your node filters to include multiple data stream paths with one filter. To learn how to set up OPC UA sources for your SiteWise Edge gateway, see OPC UA data sources for SiteWise Edge.

Note

AWS IoT SiteWise restarts your SiteWise Edge gateway each time you add or edit a source. Your SiteWise Edge gateway won't ingest data while it's restarting. The time to restart your SiteWise Edge gateway depends on the number of tags on your SiteWise Edge gateway's sources. Restart time can range from a few seconds (for a SiteWise Edge gateway with few tags) to several minutes (for a SiteWise Edge gateway with many tags).

The following table lists the wildcards that you can use to filter OPC UA data sources.

OPC UA node filter wildcards
Wildcard Description
* Matches a single level in a data stream path.
** Matches multiple levels in a data stream path.
Note

If you configure a source with a broad filter and then later change the source to use a more restrictive filter, AWS IoT SiteWise stops storing data that doesn't match the new filter.

Example scenario using node filters

Consider the following hypothetical data streams:

  • /WA/Factory 1/Line 1/PLC1

  • /WA/Factory 1/Line 1/PLC2

  • /WA/Factory 1/Line 2/Counter1

  • /WA/Factory 1/Line 2/PLC1

  • /OR/Factory 1/Line 1/PLC1

  • /OR/Factory 1/Line 2/Counter2

Using the previous data streams, you can define node filters to limit what data to include from your OPC UA source.

  • To select all nodes in this example, use / or /**/. You can include multiple directories or folders with the ** wildcard characters.

  • To select all PLC data streams, use /*/*/*/PLC* or /**/PLC*.

  • To select all counters in this example, use /**/Counter* or /*/*/*/Counter*.

  • To select all counters from Line 2, use /**/Line 2/Counter*.